Revised – 2026.01.27

Please also refer to “Part IV – REGULATORY REQUIREMENTS” for additional requirements.

Housing and Dining Facilities (HDS) has adopted amendments for all HDS facilities. Confirm applicable standards with Project Representative on a per Project basis.

Refer to HDS amendments within each section below.

TABLE OF CONTENTS – DIVISION 23 – ELECTRICAL
26 05 00 – COMMON WORK RESULTS FOR ELECTRICAL
26 05 19 – LOW–VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
26 05 33 – RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
26 05 53 – IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 09 23 – LIGHTING CONTROL DEVICES
26 22 00 – LOW–VOLTAGE TRANSFORMERS
26 24 13 – SWITCHBOARDS
26 24 16 – PANELBOARDS
26 27 26 – WIRING DEVICES
26 29 00 – LOW–VOLTAGE CONTROLLERS
26 32 13 – ENGINE GENERATORS
26 33 53 – STATIC UNINTERRUPTIBLE POWER SUPPLY
26 51 00 – INTERIOR LIGHTING
26 56 00 – EXTERIOR LIGHTING

26 05 00 – COMMON WORK RESULTS FOR ELECTRICAL

PART 1  GENERAL

A. Codes and Standards:

1. The design and construction of all University Work shall comply with the current Office of the State Architect (OSA) adopted edition of the National Electric Code (NEC), International Energy Conservation Code (IECC), National Fire Protection Association (NFPA), Occupational Safety and Health Administration (OSHA) requirements in 129 CFR 1910, and Underwriters Laboratories (UL), as well as other codes and standards as listed in the introduction.

2. Projects shall comply with the latest edition of the Colorado Model Electric Ready and Solar Ready Code. This may require additional panel space to accommodate the replacement of combustion equipment with equivalent future electric equipment, and additional infrastructure for future PV Solar and electric vehicle charging.

3. Projects shall comply with the performance criteria outlined in Regulation 28 from the Colorado Air Quality Control Commission regarding Building Benchmarking and Performance Standards. This regulation outlines specific EIU Intensity Targets by building type.

4. All electrical Work at Colorado State University (CSU) shall be performed by a State of Colorado Licensed Contractor or a Maintenance Electrician under the supervision of a Licensed Electrician.

B. Design:

1. Refer to Chapter 03 – Drawings and Design Requirements by Discipline.

C. Utilities:

1. Refer to Division 33 – Utilities for requirements related to domestic water, sanitary, stormwater, natural gas, chilled water, heating water, steam, electrical and communication utilities. 

2. All incoming building utilities must be provided with separate meters, along with power and data drops, if required.

a. Refer to 33 19 00 – Water Utility Metering Equipment, 33 59 00 – Hydrocarbon Utility Metering, 33 61 33 – Hydronic Energy Distribution Metering, 33 63 33 – Steam Energy Distribution Metering, and 33 71 73 – Electrical Utility Services.

3.   For Transformers and Underground Distribution, refer to Division 33 – Utilities, 33 70 00 – Electrical Utilities.

D. Project Record Set Documents:

1. Record Drawings provided at completion of the Project must include exact routing details of concealed service and feeder conduits through a given site or building.

2.   Provide dimensional ties to all underground or under slab on grade conduits 1” and larger trade size.

26 05 19 – LOW–VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

PART 1  GENERAL

A. Conductor Sizing:

1. Branch circuits whose length from panel to first outlet exceeds 75’–0” for 120–volt circuits shall be next size larger, as recommended by the NEC for limiting voltage drop.

2. Branch circuits whose length from panel to first outlet exceeds 175’–0” for 277–volt circuits shall be next size larger, as recommended by the NEC for limiting voltage drop.

3. Minimum wire size for branch circuit conductors:

a. #12 AWG unless allowed otherwise by special permission from Facilities Management (FM).

4. Maximum wire size for service and feeder circuit conductors:

a. 500 kcmil Copper and 750 kcmil Aluminum, unless allowed otherwise by special permission from FM.

PART 2  PRODUCTS

A. Products Not Permitted:

1. Non–Metallic Cable (type NM or NM–C)

2. Metal–Clad Cable (type AC)

3. Through–the–wall boxes

4. Electrical Nonmetallic Tubing (ENT)

B. Wires and Cables:

1. Building wire and cable electrical power conductors shall be copper, insulated to 600 volts.

2. Metal–Clad Cable

a. Metal–Clad cable shall be type MC (not AC) with a full size ground wire.

i. Using the metal spiral wrap and/or drain wire as a ground is not permitted.

b. Metal–Clad cable may be used in the following applications.

i. 6’–0” or shorter for connections to motors and light fixtures.

ii. Routed from a junction box above each room, down the wall to an outlet.

iii. Branch circuit home–runs back to the panel must be in conduit.

3. Aluminum wire shall be allowed under the following conditions:

a. Aluminum wire can be used for service feeders from building service transformer to main distribution panel/center, and for feeders from main distribution panel/center to panel boards.

b. The aluminum wire shall be terminated in compression lugs or compression copper pigtail adapters.

i. A compression copper pigtail adaptor shall have the barrel designed of high strength aluminum alloy and the pigtail of high conductivity copper.

ii. Compression of lugs and pigtail adapters shall be with a Burndy type hydraulic compression tool or equal.

c. Aluminum wire shall be no smaller than #1 AWG and no larger than 750 kcmil.

i. If aluminum phase conductors are used, copper or aluminum grounding conductors shall be sized per NEC.

PART 3  EXECUTION

A. Meter Wiring

1. Provide dedicated 120 volt hardwire connection and a Category 5 data drop for chilled water meter.

2. Provide a Category 5 data drop for the steam meter.

B. Branch Circuits and Color Coding:

1. Conductor Insulation Color:

Conductor

120/208V

3 Phase

277/480V

3 Phase

Phase A

Black

Brown

Phase B

Red

Orange

Phase C

Blue

Yellow

Neutral

White

Gray

Ground

Green

Green

26 05 33 – RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

PART 1  NOT USED

PART 2  PRODUCTS

A. Acceptable Products:

1. Wireway System:

a. Wiremold Legrand

b. Monosystems

c. Or approved equal

PART 3  EXECUTION

A. Raceways:

1. Raceways shall be EMT, RMC, PVC for all concealed Work and for exposed Work where allowed.

2. For remodels, surface metal raceways shall be used in finished areas.

a. Exposed EMT and RMC are not allowed unless allowed otherwise by special permission from FM.

3. Minimum size of power conduits shall be 3/4” to allow for future installation of additional circuits.

a. Minimum size of lighting conduits shall be 1/2”.

4. The minimum distance from the top of the ceiling grid to the low point of the pipe and/or conduit shall be 4” to 6” to facilitate replacement and/or removal of ceiling panels.

B. Raceway Supports:

1. Raceways shall not be supported from or attached to ceiling support wires.

2. Raceways or equipment shall not be suspended from steam, water, or other piping, or ductwork. Provide independent and secure support methods.

3. Care shall be taken to avoid placing raceways where they shall be subjected to excessive heat.

a. Locate all raceways a minimum of 12” from flues, steam lines, hot water lines, etc.

C. Underground Conduits:

1. Where PVC conduit is used in underground applications or concrete slab, rigid metal conduit (RMC) with PVC jacketing or tar coating or continuous strand epoxy fiberglass shall be used for riser bends and extensions to above grade or through–slab locations.

a. Where runs exceed 100’–0” in length between openings, RMC or strand–epoxy fiberglass elbows shall be used for change in direction of 45 degrees or more.

2. Grade mounted junction boxes are not permissible, unless allowed by special permission from FM.

D. Grounding:

1. Provide a separate, insulated equipment–grounding conductor in all lengths of branch circuit and feeder conduits.

E. Locations for Outlets:

1. Provide electrical outlets of 115 volt, 20 amps at the following locations:

a. Mechanical and electrical rooms

b. Within 25 feet of rooftop units

c. Next to lawn sprinkler controllers

d. Two duplex outlets on dedicated circuits shall be provided in all janitor closets.

2. Convenience outlets should be located at approximately 25’–0” intervals in corridors and located at stair landings to accommodate cleaning equipment.

a. Outlets should also be located near office doors where they will not be covered by furniture.

26 05 53 – IDENTIFICATION FOR ELECTRICAL SYSTEMS

PART 1  NOT USED

PART 2  NOT USED

PART 3  EXECUTION

A. Equipment Identification:

1. Label all panels, disconnect switches, motor starters, control stations and special devices furnished under Division 26.

a. Labels shall be etched lamacoid (black with white core) with minimum 1/8” high letters and shall indicate area served and equipment served.

b. Labels shall be attached to equipment with sheet metal screws.

c. Labels for emergency equipment shall be the same as above except Life Safety tags shall be yellow with white core; and Optional Standby tags shall be orange with white core.

2. Label all junction, splice and terminal boxes and device plates.

a. Labeling shall include panel name and circuit number.

b. Locate label on inside and outside of all device plates and covers.

c. Locate label on outside of junction boxes above ceilings or in unfinished areas.

d. Use label maker P–Touch or equal.

3. Cover plates of junction and pull boxes associated with raceways for Emergency Power Systems shall be painted red and labeled emergency.

4. Arc flash and shock hazard appropriated personnel protection PPE requirement warning tags shall be supplied for all equipment from the building service transformer to the branch panels, per Chapter 03 – Drawing and Design Requirements by Discipline.

5. HDS – All parking and pedestrian pole lights shall be labeled.

a. The label must contain the panel name and circuit number.

26 09 23 – LIGHTING CONTROL DEVICES

PART 1  GENERAL

A. Context:

1. The intent of this section is to provide guidelines for lighting control performance, products and application on CSU’s campuses.

2. Residential dwelling and sleeping units, private offices, open office areas, conference rooms, laboratories, commercial kitchens, restrooms, classrooms, break rooms, custodial closets, storage rooms, electric rooms and mechanical rooms shall be controlled by stand–alone Systems.

B. Codes and Mandates:

1. All CSU projects shall have a lighting control design conforming to the current OSA adopted edition of the IECC and the guidelines outlined in this section.

2. Where requirements are not equal, the stricter requirement shall be used.

3. Projects pursuing LEED certification shall still conform to the guidelines of this section. If control technologies are being considered that are not referenced in this section, consult with FM Electrical Engineer for approval.

C. Network Compatibility:

1. In general, Lighting Control Systems shall not be networked to the Building Automation System (BAS). However, specified Manufacturers and their products shall be able to communicate using native BACnet for future connectivity.

2. Each panel shall be able to connect to the BAS network and shall allow programming of groups and viewing of status via the BAS software.

a.  Small site lighting panels shall not be required to be BACnet compatible.

D. Document Requirements:

1. Electrical lighting plans shall include the following:

a. Distinct symbology to distinguish between different types of occupancy sensors.

i. Technology:

a) Infra–red vs ultrasonic vs. dual technology

ii. Application:

a) Corridor vs. large room vs. small room sensors

iii. Wiring:

a) Line voltage vs. low voltage vs wireless

iv. Location and orientation of each product

b. Typical wiring diagrams of lighting control devices in different applications.

c. Interconnection diagrams per major Subsystem showing proper wiring.

d. A lighting control matrix to indicate lighting control performance.

e. A switch schedule for all low voltage switches identifying what each switch controls.

2. Closeout Documents shall include:

a. Lighting Controls Manual included in the O&M Manual.

b. As–Built Record Drawings showing final installed condition.

c.  Any Lighting Control Drawings produced by the Lighting Controls Manufacturer or Vendor.

d. A record of the schedules/settings programmed into the Lighting Controls System.

E. Quality Assurance:

1. On new construction Projects, a lighting commissioning agent shall be utilized to ensure that the Lighting Control System is fully programmed and operating at its peak performance level.

PART 2  PRODUCTS

A. Performance Specifications:

1. In general, automatic lighting controls shall be vacancy sensor type, “Manual On, Auto Off”.

a. Typical auto off time is after 20 minutes of non–activity.

2. Automatic time switch control devices (typically used in common public areas such as lobbies and vestibules) shall include a manual override switching device in a readily accessible location, near the lights being controlled.

3. In general, automatic daylight harvesting controls shall utilize continuous dimming (versus stepped dimming) in normally occupied areas.

B. Terms:

1. Building Control System:

a. A central Control System controlling a large number of lighting zones through the inputs such as occupancy sensors, time clock programming, manual wall stations, etc.

b. May consist of either one lighting control panel or a group of networked control panels.

2. Manual Control:

a. Control method requiring human intervention to regulate electric lighting, typically through a wall switch.

3. Occupancy Sensor:

a. A control device that detects the presence or absence of people and causes lighting to be regulated either on or off.

4. Photo Sensor:

a. A control device that detects the presence of visible light and causes lighting to be regulated either on, off or dimmed.

5. Relay Control Panel:

a. Central time–based controller program using relays and schedules.

6. Stand Alone Devices:

a. Wall or ceiling mounted occupancy sensor wired directly to lighting fixtures (through a power pack, as required), with no connectivity to devices outside of this room.

C. Products:

1. Lighting Control Network Cable:

a. Cable shall be plenum rated, violet in color with pre–terminated jacks tested by the factory.

2. Occupancy Sensors:

a. Occupancy sensors shall be capable of being converted to vacancy sensors. Auto on shall only be allowed per the IECC allowable exceptions.

b. Dual technology sensors shall be provided for all offices, conference rooms and other occupied workspaces.

c. Passive infrared sensors may be used in common and storage areas, high–bay and exterior applications.

d. Ultrasonic–only sensors may be used in corridors, restrooms and private offices where coverage requirements are met.

e. Wall box sensors shall be installed in smaller rooms, so that the majority of the sensor coverage is confined to the room and shall provide 100% coverage of the room with minimal coverage of any adjacent corridor.

f. Minimize the number of devices required in a room for ease of maintenance.

g. All components shall be UL listed offer a five–year warranty and meet all state and local applicable code requirements.

h. Ceiling sensors shall be located a minimum of 4’–0” from mechanical vents.

i. Ceiling sensors shall be located a minimum of 2’–0” from walls.

j. Sensor timeout shall be set to 20 minutes, typical.

3. Photocells:

a. Exterior photocells shall be outdoor–rated and operate within temperature ranges from –20 °F to 90 °F and be sealed against humidity.

b. Twist lock photocells on pole lighting shall conform to ANSI C136.41 standards.

4. Room Controllers:

a. Acceptable Products:

 i. Acuity Brands: nLight – Cat 5 wiring

ii. Wattstopper Digital Lighting Management – Cat 5 wiring

iii. Crestron (Athletics only)

5. Wireless Systems:

a. Acceptable Products:

i. Acuity Brands: nLight Air

ii. Crestron

iii. Audacy

6. Panel–based Time Control Processor (brain of the Relay Panel):

a. The clock module shall provide astronomic capabilities, time delays, blink warning, daylight savings and holiday functions and shall include a back–up for the clock function and EEPROM for program retention.

b. Lighting control panels shall have remote monitoring and programming capabilities via BacNet IP protocol.

c. Provide data outlet at each lighting control panel for connection to CSU Utilities Server.

d. Acceptable Products:

i. Acuity Brands: LC&D GR 2400

ii. Wattstopper: Digital Lighting Management

iii. Crestron

7. Small Site Lighting Control Panel (Astronomic Time Clock/ Photocell):

a. Acceptable Products:

i. Intermatic

ii. Tork

iii. Or approved equal

8. Site Lighting Control Panel with Wireless Dimming:

a. Acceptable Products:

i. Hubbell WiScape

ii. Acuity Brands: nLight

iii. Or approved equal

9. Relay Panels:

a. Acceptable Products:

i. Acuity Brands: LC&D GR2400 & Blue Box

ii. Wattstopper: Digital Lighting Management

iii. Crestron

10. Daylighting Controls:

a. Provide daylight controls to control lighting as indicated on plans.

i. Daylight zones shall be designed such that lights in the daylight zone are controlled independently of general lighting

b. Maintain a specified foot candle level based on the contribution of natural and artificial light.

c. Daylight zones under skylights shall be controlled separately of daylight zones adjacent to vertical fenestrations.

d. Any tools or software required to adjust the System shall be provided as part of the System package.

i. This excludes foot–candle meters.

11. Dimming Panels (for use in large classrooms and conference rooms, auditoriums, etc.):

a. Dimming panels shall be compatible with the lamp source they are dimming. LEDs are especially sensitive to incompatibilities.

i. LED fixtures with integral dimmers shall not be dimmed from a dimming panel.

b. All dimmers shall be de–rated to no more than 80% of rated capacity.

c. Rooms with indication of preset stations shall be provided with engraved presets, to be approved by the Project Representative, or touch screens with the ability to create and label presets.

i. Preset creation shall be limited to select users and password protected.

d. Conference rooms and classrooms over 500 square feet shall include the ability to communicate with the Audio Visual System.

e. Acceptable Products:

i. Acuity Brands: Fresco

ii. Crestron

iii. Philips Strand

PART 3  EXECUTION

A. Lighting Control Method by Room Application – In general, the following room types shall be controlled as follows:

1. Private Office:

a. Manual dimming and control by the entrance.

b. Standalone vacancy sensor (Manual On, Auto Off), typically dual technology, located at the switch or preferably within the light fixture itself for improved functionality.

2. Open Office:

a. Manual control by the entrances, grouping the lights into separate zones.

b. Ceiling or fixture–embedded vacancy sensors to turn lights off, typically dual technology.

3. Public Restrooms:

a. Standalone occupancy sensor (Auto On, Auto Off), typically ultrasonic

4. Conference Rooms:

a. Manual dimming and control by entrance, with control zones for presentation purposes, as necessary.

b. Ceiling or fixture–embedded vacancy sensors to turn lights off, typically dual technology.

5. Classrooms:

a. Manual dimming and control by entrance.

b. AV pedestal manual dimming and control with scene selection, as necessary.

c. Minimum two lighting control zones – one at the teaching wall, one at the student seating area.

d. Ceiling or fixture–embedded vacancy sensors to turn lights off, typically dual technology.

6. Lobbies, Foyers and Entryways:

a. Ceiling or fixture–embedded occupancy sensor (Auto On, Auto Off)

b. Time schedule operated lighting as required by end user.

7. Breakrooms:

a. Manual control by the entrance

b. Ceiling vacancy sensor to turn lights off, typically dual technology. 

8. Dining Halls:

a. Consider scheduled programmable On–times with required Manual control to initiate program (this would prevent lights from coming on during a Holiday Break when Dining Hall is not in use.) 

b. Consider separating Food Prep, Serving, and dining areas for more control. 

c. Locate manual wall stations at convenient entry points to easily initiate the programmed On–times, and manually override the Off time if the cleaning crew were to finish early. 

9. Commercial Kitchens:

a. Manual On, Manual Off 

10. Corridors

a. Ceiling or fixture–embedded occupancy sensor (Auto On, Auto Off)

b. Use of night lights shall be limited. Not every emergency light shall be a night light.

11. Stairwells

a. Ceiling or fixture–embedded occupancy sensor that will dim down to 10% when unoccupied.

b. Upon loss of power, light fixtures shall turn on to full bright.

12. Laboratories:

a. Manual On, Manual Off, Dimming permissible

13. Mechanical/Electrical Rooms:

a. Manual On, Manual Off

14. Custodial Closets:

a. Vacancy sensor (Manual On, Auto Off)

15. Storage Rooms:

a. Vacancy sensor (Manual On, Auto Off)

16. Library Stacks and Warehouse Storage Areas:

a. Fixture embedded occupancy sensors for Auto On, Auto Off.

17. Residential Sleep and Dwelling Units

a. Manual on, Manual off with dimming capabilities

18. Study Room

a. Standalone vacancy sensor (Manual On, Auto Off), typically dual technology

b. If the switch is not readily accessible by the entrance, an occupancy sensor is acceptable.

19. Parking Garages:

a. Garage lighting shall be reduced to 30% when no activity is detected for 20 minutes. Fixtures with integral occupancy sensors are recommended.

b. Daylight transition zone lighting shall be controlled separately by time clock such that these lights are on during the day and off at night.

c. Light fixtures adjacent to the perimeter of an open structure garage may be controlled with automatic daylight harvesting controls.

20. Exterior Site Lighting:

a. See Section 26 56 00 Exterior Lighting for Exterior Lighting Control section.

PART 4  TESTING AND COMMISSIONING

A. Projects shall include a Manufacturer Authorized Service Technician to meet the Contractor on–site prior to installation of the System.

1. The Manufacturer authorized technician shall provide a full set of Lighting Control Drawings and review device placement, switch locations, wiring requirements and any other information critical to the installation of the System.

B. Functional testing shall be commissioned by the Manufacturer’s factory Authorized Technician or an Independent Consultant authorized by Manufacturer to work on Lighting Control System.

1. Project Representative from Operations and Maintenance shall be present at Contractor functional testing.

C. Documentation shall be provided to the Project Representative certifying that the installed lighting controls perform in accordance with the design.

D. Provide documentation for all daylight harvesting zones including desk top readings with lights off, lights at full and lights under daylight harvesting control.

1. Include time, date and general weather conditions (e.g. full sun, cloudy) include information on the testing device, foot–candle meter, etc. used.

2. All testing and verification shall be conducted by Factory Trained Technician.

a. Test reports shall be signed by the Technician.

E. The following shall be verified:

1. Occupancy and daylight sensors are located, installed and adjusted as intended by the factory and the Construction Documents.

2. The sensors and relay panels interact as a complete and operational System to meet the design intent.

3. Programmable schedule controls have been programmed to the building representative’s satisfaction.

4. Placement and sensitivity of adjustments for photo sensor controls reduce electric light based on the amount of usable daylight in the space.

5. The Manufacturer shall provide a factory authorized technician to train Project Representative’s personnel with the operation, use, adjustment and problem–solving diagnosis of the occupancy sensing devices and Systems.

F. Provide an additional follow–up programming session within three months after the initial programming.

G. Provide accurate As–Built Drawings reflecting the latest programming requirements.

26 22 00 – LOW–VOLTAGE TRANSFORMERS

PART 1  GENERAL

A. Transformers (dry–type):

1. Transformers of not over 600 volts may be dry–type, indoor when installed in accordance with Article 450 of the NEC.

2. Dry–type transformers shall not be rigidly attached to the building structure, surfaces.

a. Flexible conduit shall be used to connect the transformer to the building Wiring System.

3. Transformers larger than 15kVA and transformers designed to be floor–mounted shall be set on resilient vibration–isolating material equal to Korfund “ElastoRib”.

a. Sufficient quantity of resilient materials shall be used so as not to exceed the Manufacturer’s recommended pound per square inch loading factor.

4. Dry–type transformers shall be sized to provide the code calculated demand load.

5. Aluminum windings are acceptable.

B. Grounding:

1. Transformer neutrals for the secondaries of separately derived Systems shall be grounded to the nearest available effectively grounded structural member or the nearest available effectively grounded water pipe, as required by NEC 250.

a. Where neither of these grounding electrodes are available, the secondaries shall be grounded by way of a grounding electrode conductor between the secondary neutral and grounding buss at the service entrance equipment.

PART 2  PRODUCTS

A. Acceptable Manufacturers

1. Square D

2. ABB

3. Siemens

4. Eaton

26 24 13 – SWITCHBOARDS

PART 1  GENERAL

A. Service and Distribution Switchboards:

1. Provide fully rated main bus in all switchboards.

a. Tapered bus assemblies not permitted.

2. Service entrance design shall be based upon fault current figures calculated in accordance with the requirements for Short Circuit Calculations in Chapter 03 – Drawings and Design Requirements by Discipline.

3. Provide for voltmeter, ammeter and other like functions with a switchboard mounted power monitor.

4. Buildings that require sub–metering systems for applicable Energy Codes shall utilize a high–density metering system.

PART 2  PRODUCTS

A. Brand Specific Product:

1. Square D Co.

2. Sub–Metering: Square D Power Logic HDPM6000

26 24 16 – PANELBOARDS

PART 1  NOT USED

PART 2  PRODUCTS

A. Brand Specific Product:

1. Square D Co.

B. Panelboards:

1. Fault current ratings for all new panelboards and enclosed circuit breakers shall be submitted to FM Electrical Engineer for approval prior to the installation of the equipment.

2. Provide ample spare 3/4” or larger conduits out of panels into a wireway or junction boxes.

a. Run empty conduits to accessible spaces.

b. Provide conduits of sufficient capacity to carry all available spares from panel to above wall or drop ceiling.

3. All lighting and power panels shall be specified to provide minimum of 30% spare breaker space. This requirement does not mean to provide 30% of spare bus ampacity.

a. Residential units with in–unit sub–panels shall have 10% spare breaker space, but no less than two spare breakers.  

4. A/E shall provide panel schedules on Construction Documents.

a. Final typed schedules to be provided by the Contractor shall correspond to final CSU room number schedule.

5. Provide fronts with hinged trim, “door in door” construction for one–person access to wiring area.

a. All panel covers shall be factory painted with low gloss enamel (not flat wall paint) suitable for metal.

b. Field painting shall not be permitted.

6. The switching of lights from lighting panels is not acceptable.

7. Panelboard circuit directories shall be updated for every project, which involves new circuits, reassignment of circuits or even just renumbering of rooms.

26 27 26 – WIRING DEVICES

PART 1  GENERAL

A. Electrical Devices:

1. All electrical devices such as switches and receptacle outlets shall be specification grade suitable for high abuse areas.

2. Duplex convenience receptacle outlets shall be rated 20 ampere, minimum. Lighting switches shall be rated 20 ampere, 120/277 volt at a minimum.

3. All electrical devices shall have a tape label attached to the inside of the box and on the outside of the cover to identify the branch circuit serving the device.

a. The tape label shall be adhesive marking tape with typed black letters on clear background, 3/8” Brother P–Touch or approved equal.

4. Shallow boxes for electrical devices are not permissible, unless allowed by special permission from FM.

B. Locations for Receptacles:

1. Provide electrical receptacles of 115 volt, 20 amps at the following locations:

a. Mechanical and electrical rooms

b. Within 25’–0” of rooftop units

c. Next to lawn sprinkler controllers

2. Convenience outlets shall be located at approximately 40’–0” intervals in corridors and located at stair landings to accommodate cleaning equipment.

a. Outlets shall also be located near office doors where they won’t be covered by furniture.

3. Provide GFI protection for all restrooms and custodial closets with mop sinks.

a. The circuits in bathrooms, hallways, and custodial closets shall be separate from offices to avoid computer power quality problems.

4. Provide an accessible NEMA 6–50 outlet located in the mechanical room for a welder.

C. Automatic Receptacle Control (as required by Energy Code):

1. Utilize half–controlled duplex receptacles, where one outlet is controlled by the occupancy sensor and the other outlet is constant hot.

2. For receptacles in modular furniture, use circuit “D” as the controlled receptacle. Modular furniture is typically an 8–wire circuit infeed whip with A, B, C and D labeled receptacles.

D. Special Receptacle Outlets:

1. Any special purpose electric outlets supplied by the Electrical Contractor shall be provided with matching cord caps.

a. If not installed on equipment, these cord caps shall be provided to FM prior to final acceptance of the building.

b. Outlets shall conform to NEMA configurations.

2. Use specification grade devices with all–brass Grounding Systems.

3. Outlet boxes shall be minimum 4” nominal square or octagonal, except that cut–in boxes shall be allowed in masonry walls.

a. Sectional or handy boxes not permitted.

E. Light Switches:

1. Use specification grade devices suitable for high abuse areas.

2. Refer to Chapter 03 – Drawings and Design Requirements by Discipline for more information.

26 29 00 – LOW–VOLTAGE CONTROLLERS

PART 1  NOT USED

PART 2  PRODUCTS

A. Acceptable Products:

1. Fractional horsepower motor starters:

a. Sprecher + shuh

b. Square D Company

c. ABB

d. Eaton

2. Solid state reduced voltage starters:

a. Square D Company

b. ABB

c. Rockwell Automation

d. Consider using variable frequency drives instead of reduced voltage starters.

3. Variable frequency drives:

a. ABB

b. Rockwell Automation

c. Yaskawa

d. Must be capable of network communication using BACnet protocol.

B. Motors, Starters and Protection:

1. All motor disconnects shall be heavy duty rated.

2. All motors 20 horsepower and larger shall be power factor corrected to a minimum of 95% at design load. HVAC Systems may be corrected at the motor control center.

3. For motors 5 horsepower and larger, devices to protect the motor against loss of phase (single phasing protection) shall be provided.

a. Devices to meet this requirement shall be of the current sensing type and may be provided either as an integral part of the thermal overload or as a separate device.

b. Units shall have manual reset and adjustable limits.

4. Solid–state reduced voltage starters or variable frequency drives shall be provided for all motors 20 horsepower and larger. The starter shall have current limitation adjustable between 150% and 425% of all load current.

a. Smooth, soft start shall be accomplished by adjustable acceleration ramp time between 0.5 and 30 seconds via a potentiometer.

b. Solid–state overload with external manual reset shall be provided.

c. Starters shall be inhibited when loss of any phase is sensed.

d. Diagnostic LEDs mounted externally shall indicate phase loss, control power, controller on, overload trip, and shorted SCRs.

e. Optional features to be included are hand–off–auto selector switch with red, green, amber pilot lights and push–to–reset button and isolation contractor.

5. All motors to be provided with external overload running protection. This is in addition to any ‘built–in’ protection inherent in the motor.

6. Motors controlled by variable frequency drives shall utilize an SGR– “shaft grounding ring” in order to prevent electrical damage to the motor bearings.

a. Consult with FM Electrical Engineer if another form of bearing isolation is being considered.

7. Rooftop unit equipment shall be provided with an integral disconnect.

a. Project Team to coordinate with mechanical specification for inclusion of this requirement.

8. Rooftop unit equipment shall be provided with an integral receptacle, not connected to the HVAC equipment’s power circuit.

a. The Electrical Contractor shall run another circuit to this receptacle separate from the RTU circuit.

b. Project Team to coordinate with mechanical specification for inclusion of this requirement.

C. Variable Frequency Drives (VFD):

1. All motor applications at or above 5 horsepower require the use of a variable frequency drive controlled by an input from the BAS (for energy management purposes).

2. VFD General Features:

a. Full load VFD efficiency shall not be less than 95%. System power factor shall be 95% or better across the operational speed range.

b. Enclosure type:

i. NEMA 1, or as required

ii. Provide cabinet ground lug in VFD enclosure.

c. Rated and sized for 5,000’ elevation operating condition.

d. Automatic soft start feature to start motor at lowest speed and ramp slowly up to required speed on start–up and for any abrupt changes in required speed.

i. Provide a minimum of two acceleration and deceleration ramps adjustable from 0.1 seconds to ten minutes.

e. VFD bypass device is not required.

3. VFD Protective Features:

a. Input line fuse or circuit breaker with door interlock disconnect.

b. Provide input line filters sized so that total harmonic voltage distortion is less than 5%.

c. Automatic restart circuitry to restart motor after a momentary or sustained power failure, phase loss, or non–damaging fault trip.

i. No more than five restart attempts shall be allowed before lockout.

ii. Auto restart feature shall be switch defeatable.

iii. For all applications, the VFD shall be capable of restarting into a forward or reverse rotating motor at any speed.

iv. The VFD shall also incorporate a five second control power loss ride through to eliminate nuisance tripping.

4. VFD Interface Features:

a. Cover mounted alphanumeric display with keypad control panel.

b. Provide manual speed adjustment, HAND–OFF–AUTO switch and 4–20 milliamp and 0–10 volt speed reference analog inputs, fully isolated and suitable for grounded or ungrounded input signal.

26 32 13 – ENGINE GENERATORS

Please also refer to “Part IV – REGULATORY REQUIREMENTS” for additional requirements.

PART 1  GENERAL

A. Generators shall be either natural gas or diesel generator sets.

1. Verify with FM Engineering which fuel source is preferred depending upon the location.

a. HDS – Wherever logistically feasible and cost-effective, generators shall be natural gas.

2. Generator shall have rated kW/kVA output at 5,000’ above sea level.

3. Coordinate requirements with Project Representative.

4. Do not locate generator exhaust in close proximity to HVAC air intakes.

B. Sound Limitations:

1. The noise generated by the installed diesel generator set operating at 100% load shall not exceed the following sound pressure levels in any of the indicated frequencies when measured at a distance of 75’–0” from the end of the exhaust and air intake piping directly along the path of intake and discharge for horizontal piping; or at a radius of 35’–0” from the engine at 45 degrees apart in all directions for vertical piping.

2. Submit data to demonstrate compliance with these sound limitation requirements.

a. Also, submit certification from the Manufacturer stating that the sound emissions meet the Specifications.

Frequency Band

(Hz)

Maximum Acceptable

 Pressure Level

(Decibels)

 

20–75

81

75–150

71

150–300

64

300–600

58

600–1,200

55

1,200–2,400

54

2,400–4,800

54

4,800–10,000

56

3. HDS – The noise generated by the installed generator set operating at 100% load shall not exceed level 3 hospital grade.

PART 2  PRODUCTS

A. Acceptable Products

1. Cummins

2. Cat

3. Kohler / Rehlko

B. Products Not Permitted:

1. Generac

C. Generator

1. The diesel generator main fuel tank shall have capacity to supply fuel to the engine for an uninterrupted 24 hour period at 100% rated load without being refilled.

2. Remote alarm panel: provide a remote alarm panel in accordance with NFPA 110 Level 1.

a. The panel shall be supplied with an enclosure.

3. Provide programmable exercise clock timer.

D. BAS Alarms:

1. Provide a dry contact for the following alarms:

a. Generator shutdown alarm

b. Generator running

c. Transfer switch to emergency power

d. HDS – Provide tie–in back to HDS Facilities Control Shop.

E. Remote Monitoring System:

1. Provide a mobile and web application monitoring with capability to notify designated users of Warnings and Faults via email or text.

2. Acceptable Products:

a. Cummins Power Command Cloud

b. Cat VisionLink

c. Kohler OnCue

F. Local Software Access:

1. Provide a software package in Windows Explorer format that can be used with a personal computer (PC) to be able to access and download alarms, setting, and run times information and equipment history.

PART 3  EXECUTION

A. Performance test shall be a 100% load test to include resistive and reactive load to nameplate rating at 80% power factor using resistive and reactive load banks.

B. Engine generator set shall be operated at 75% of rated load for at least two hours and then 100% rated load for at least four hours.

1. In addition, a full load acceptance test of 100% of rated load shall be applied to the generator with voltage and frequency stabilization occurring per Specifications.

26 33 53 – STATIC UNINTERRUPTIBLE POWER SUPPLY

PART 1  GENERAL

A.  Uninterruptible Power Supply (UPS):

1. UPS shall be a true on–line double conversion UPS, using IGBTs.

2. Provide a battery back–up cabinet utilizing either lithium–ion or lead–acid batteries, with a minimum run time of 5 minutes.

3. UPS shall include an external maintenance bypass cabinet, or some other means of maintaining the UPS without causing the critical load to be shut down.

4. Provide a dry contact for a general UPS alarm back to FM BAS Shop for monitoring.

26 51 00 – INTERIOR LIGHTING

PART 1  GENERAL

A. All light intensity design shall be done in accordance with the recommendations of the Illuminating Engineering Society of North America.

B. Lighting Design Drawings shall include the following:

1. Lighting Fixture Schedule showing information pertinent to LED sources, including lumen output, wattage, lumens per watt ratio, color temperature, etc.

2. Power Density schedule showing watts, area and watts–per–square foot density for all major area types.

3. Lighting control matrix indicating how lighting is controlled in each typical room type (private office, open office, stairwells, corridors, etc.)

PART 2  PRODUCTS

A. Interior Luminaires:

1. Standard luminaire for interior office and classroom spaces is the 2’ x 2’ or 2’” x 4’, troffers or flat panels.

2. Other types of acceptable fixtures (where deemed appropriate by the designer) include:

a. Recessed “cans”

b. Wall washing fixtures

c. Wrap–around fixtures

3. Provide a minimum of 10 foot–candles in stairwells.

4. LED luminaire output shall be a 3500K color temperature and minimum Color Rendering Index (CRI) of 80.

a. HDS – All areas within dining facilities shall be at a 4000k color temperature and minimum Color Rendering Index (CRI) of 80.

B. Lamps:

1. Incandescent lamps are prohibited in general.

a. For special cases where incandescent lamps are essential, incandescent fixtures may be specified only with approval from FM Engineering.

2. FM prefers that older lamp technologies (metal halide, fluorescent, compact fluorescent), be removed and replaced with a completely new LED fixture.

a.  However, there are cases where existing installation methods may make this impractical.

b.  If LED lamps are proposed, coordinate with FM Electrical Engineer to determine if acceptable.

3. LED retrofit lamps shall not be installed in recessed troffer or can light fixtures which do not have integral air circulation in the housing of the fixture.

4. LED retrofit lamps that replace existing T8 fluorescent lamps shall be of the Type “B” that bypasses the fluorescent ballast.

a. The fluorescent ballast shall be removed from the fixture.

5. LED lamps shall be manufactured from a company that has been in business for five years or longer.

6. LED lamps shall have a minimum 50,000 hour mean life.

7. LED lamps shall have a minimum five year warranty, including the driver.

C. Exit Lights:

1. Exit light hardware shall use Light Emitting Diodes (LED) as their source of illumination.

2. Exit signs shall be ENERGY STAR compliant.

3. The use of Self–Luminous exit signs is prohibited.

a. Self–Luminous exit signs also known as radioluminescent exit signs or tritium exit signs contain tritium gas which is radioactive and toxic.

D. Emergency Lighting: Back–up power sources are listed in the following order of preference:

1. Central Battery Inverter: Most preferred option to minimize labor required for testing.

2. Local Batteries:

a. Include a self–testing automated reporting system, to meet testing and record keeping requirements of NFPA 101.

b. Exit signs may include attached or remote “frog eyes”.

c. Emergency lighting units, or “frog eyes” are preferable for reasons of maintenance and replacement costs.

d. Combination exit and emergency lighting units shall be used in back of house areas and areas deemed acceptable by the Architect, in lieu of battery back–up ballasts.

3. Generator:

a. Where sufficiently large emergency loads are required, an emergency generator may be necessary.

b. Do not specify a battery system for emergency lighting loads if a generator is on the project.

26 56 00 – EXTERIOR LIGHTING

PART 1  GENERAL
 
A. CSU will meet or exceed the City of Fort Collin’s Night Sky Initiative of outdoor lighting best practices. This includes but is not limited to the following requirements:

1. Outdoor lighting shall be down direction and fully shielded.

2. Nominal color temperature shall not exceed 3000 Kelvin.

3. Exterior location luminaires shall not exceed the BUG (Backlight, Uplight and Glare) ratings for the Lighting Zone based on campus location:

a. Main Campus:

i. LZ2: B3, U1, G1

b. South Campus:

i. LZ2: B3, U1, G1

c. Foothills Campus:

i. LZ1: B3, U0, G1

B. Campus design foot–candle levels are as follows:

1. Parking lots:

a. 0.2 fc Minimum

2. Roadways:

a. 0.3 fc Minimum

3. Sidewalks:

a. 0.5 fc Minimum

C. Conductors feeding pole–mounted luminaires shall be THWN stranded copper in minimum 1” PVC underground conduit.

1. Conductors and conduit shall be sized so that the voltage drop from the last over–current device to the luminaire is limited to no more than 3%.

D. Consider routing of spare conduit to pole lights for future security camera installation or convenience power.

1. Coordinate with security camera design.

2. Refer to Division 28 – Electronic Safety and Security for additional details.

PART 2  PRODUCTS

A. Fixture Heads:

1. Pedestrian Walkways Fixtures – Older Areas, Post Top:

a. American Electric Lighting, Contempo Series

i. 72W, 3000K, Type II, 3792 lumens

ii. Catalog # 245L–20LEDE10–vtg–3K–R2–GL–PCS

b. Spaulding Peachtree Series

i. 64W, 3000K, Type II, 4010 lumens

ii. Catalog #PT–3F 28L3K–3G–vtg–GR–Pvtg

c. Or approved equal

2. Pedestrian Walkways Fixtures – New Areas:

a. Kim Lighting, Model SAR PicoPrism, Light Grey

i. LED–1SA–SAR–x–[P35 or P70]–40L–4K–[vtg]–LG–[HSF or VSF]

b. Lithonia, Model RSX1

i. RSX1 LED P1 30K R3 MVOLT RPA [IS or VSF] [PE] DNAXD

c. Or approved equal

3. Streets/Parking Lot Fixtures:

a. Kim Lighting Model AR PicoPrism, Light Grey

i. LED – 1A–AR–x–[P35 or P70]–80L–4K–[vtg]–LG–HSF

b. Lithonia, Model RSX2

i. RSX2 LED P2 30K R3 MVOLT RPA (or MA (mast arm)) PE DNAXD

c. Or approved equal

B. Light Poles:

1. Pedestrian Light Poles – 15’–0” above ground, round tapered fiberglass, anchor–base, non–tenon:

a. Whatley, Model: TR45–15–AB–GRY–SMS–DTC

b. Lithonia, Model: RTF 16 6–1X DM19 FBC DNA

c. Or approved equal

2. Pedestrian Light Poles – 15’–0” above ground, round tapered fiberglass, anchor–base, tenon:

a. Whatley, Model: RT45–15–AB–GRY–SMS–23–50

b. Lithonia, Model: RTF 20 6–6X T20 DNA

c. Or approved equal

3. Street/Parking Lots – 30’–0” above Ground, round tapered fiberglass, anchor–base with 8’–0” mast arm:

a. Whatley, Model: TR50–30–AB–GRY–SMS–DTC/ (2) WOPAR–8–GRY

b. Lithonia, Model: RTF 30 10–5X DM19 FBC DNA

c. Or approved equal

PART 3  EXECUTION

A. Pedestrian Poles and Luminaires:

1. Pedestrian scale luminaries shall be installed on tenons on top of 15’–0” anchor base, heavy–duty, round tapered fiberglass poles.

2. The fixtures and poles shall have a smooth finish of light grey color.

3. The 15’–0” anchor base pole shall be mounted on a 24” diameter, minimum 6” high concrete caisson.

4. If poles are within 5’–0” of a parking lot curb, the caisson foundation shall be extended 30” above ground level to prevent vehicles from damaging the pole.

5. Refer to CSU Facilities Planning, Design and Construction Standards – Additional Documents for pole and foundation details.

6. Where new sidewalk or bicycle lane illumination is provided near existing 15’–0”, concrete octagonal poles, use new, matching, concrete octagonal poles with bolt–down bases, if available.

a. Foundations for these poles shall comply with the Manufacturer’s recommendations.

7. Bollard Lighting Systems are discouraged due to the abuse they sustain on campus.

B. Roadway and Parking Poles and Luminaires:

1. For parking lot and roadway applications, the luminaires shall be attached to the poles using standard 8’–0”, davit–arms.

2. The fixtures and poles shall have a smooth finish of light grey color.

3. The 30’–0” anchor base pole shall be mounted on a 24” or 30” diameter caisson, minimum of 30” high concrete caisson.

4. Refer to CSU Facilities Planning, Design and Construction Standards – Additional Documents for pole and foundation details.

C. Exterior Building:

1. Other types of luminaires used for architectural effects on or around buildings shall be subject to review and approval by FM.

a. At a minimum, architectural building lighting shall be controlled by photocell and time–clock to limit time of use.

2. Up–lighting is not allowed.

3. Exterior incandescent fixtures and HID are not allowed.

D. Controls:

1. Pole Lighting may be relay control panel, central time clock with central photocell or fixture–embedded occupancy sensor and photocell.

2. In general, pole lighting on Main Campus shall remain 100% on after dark.

3. South Campus and Foothills may consider dimming after late hours with occupancy sensor override.

4. Building Mounted Lighting:

a. Time clock with photocell

b. Consider using integral occupancy sensors to decrease light level by 30% when the area is unoccupied.

5. Parking Lot Lighting:

a. Consider using pole mounted occupancy sensors to decrease light levels by 30%–50% when the area is unoccupied.

b. All outside exterior lighting without a relay control panel–time clock will have an override switch for testing.

6. When pole installation is complete, paint stencil pole number as directed by FM Utility Services or Electrical staff. Coordinate with the FM Electrical Engineer for pole number.

END OF DIVISION